Applicable standard for radiator

NB/T 47006-2009 "Aluminum Plate Wing-type Heat Exchange"

IS012944 "Color Pain and Paint -Anti -Corruption and Protection of Protective Coating System on Steel Structure"

List of key device
MotormodelLanggao (AK100L3-4-B5),
Wan Gao (W21-3KW-4P-100L-B5T 400/690V 50Hz)
Power3
Voltage++3-400/690V(±10%)/50Hz(±5%)
Current6.4/3.7A
Small speed1450RPM
Insulation levelH
Protection levelIP55
HeatingAchievement30W(朗高)/11W(万高)
Power supply230VAC(±10%)/50Hz(±5%)
PTCPTC protection devicePTC
List of key materials
Technical parameter table (0 ~ 2000M)
Working medium42%water+50%
ethylene glycol solution
Cold wind
Thermal replacement
power (KW)
40
Flow135L/min16500m³/h
Import temperature C54.8540
Export temperature C5049.41
Design pressure MPA1
Test pressure MPA1.5
Pressure drop MPA≤0.3bar229pa
Motor3KW 4P IP55 (Langgao, Jiangte)
Wind leaf850 (Wen Fan, Modimin)
Surface treatmentCooler C4H anticorrosive+spraying powder RAL7035,                                            
rice gold C4H anticorrosive+spraying powder RAL7035,
Volume20.1L
Total约197kg
Technical parameter table (2000~3000m)
Working medium42%water+50%
ethylene glycol solution
Cold wind
Thermal replacement
power (KW)
36.6
Flow135L/min16500m³/h
Import temperature C5440
Export temperature C5049.59
Design pressure MPA1
Test pressure MPA1.5
Pressure drop MPA≤0.3bar214pa
Motor3KW 4P IP55 (Langgao, Jiangte)
Wind leaf850 (Wen Fan, Modimin)
Surface treatmentCooler C4H anticorrosive+spraying powder RAL7035,                                            
rice gold C4H anticorrosive+spraying powder RAL7035,
Volume20.1L
Total约197kg
Technical parameter

1) Altitude: 0 ~ 2000 meters

Calculation formula for heat exchange standards: P=Q·C1·ρ(T2-T1)/60

Heating power: P = 40KW

Water inlet temperature: T1 = 54.85℃

Enter the temperature: T1 = 40℃

Technical parameter table (0 ~ 2000M)
WCustomer  information
flow
40KW
Cooler typewater cooler
ChannelInsideOutside
water 55% Glyair
Heat load Q     (KW)40
Flow rate  V16500 m³/h
Inlet temp.        ( ℃ )40
Outlet temp       ( ℃ )49.41
Design press    (MPa)
Design press      (MPa)
Ambient temperature40
Press. drop229 Pa
Cal. trans. area   ( ℃ )57.050
Actual.trans. area  ( ℃ )62.033
Margin8.7%
Fin type30JC1702/5095BW2502
No. of layers7678
Pass number21
Block size(LXBXH)880*1060*100

1) Altitude: 0 ~ 2000 meters

Calculation formula for heat exchange standards: P=Q·C1·ρ(T2-T1)/60

Heating power: P = 40KW

Water inlet temperature: T1 = 54.85℃

Enter the temperature: T1 = 40℃

Technical parameter table (0 ~ 2000M)
WCustomer  information
flow
40KW
Cooler typewater cooler
ChannelInsideOutside
water 55% Glyair
Heat load Q     (KW)36.6
Flow rate  V135 L/min16500 m³/h
Inlet temp.        ( ℃ )54.61040
Outlet temp       ( ℃ )50.0049.59
Design press    (MPa)1.0(G)
Design press      (MPa)1.5
Ambient temperature40
Press. drop24.7Kpa214 Pa
Cal. trans. area   ( ℃ )28.64459.653
Actual.trans. area  ( ℃ )29.77362.033
Margin3.9%
Fin type30JC1702/5095BW2502
No. of layers7678
Pass number21
Block size(LXBXH)880*1060*100
Related Products
    No Data
Contact us
If you have any need, please contact us at any time
  • Service Hotline
    0510-85999888
  • Business inquiry
    0510-85992288
  • Email
    sales@wxjlcooler.com
  • Company address
    No. 5, Xiaguang Road, Xiaguang Road, Mashan Biomedical Industrial Park, Binhu District, Wuxi City, Jiangsu Province
  • If you have any questions, please choose the consultation category and fill in the                        project so that we can provide you with professional services
  • *Name
  • *Tel
  • *Email
  • *Company
  • If there is a custom demandor have questions about our services Please contact us